Category 5, 5e, 6, 6a and 7 Cable Standards


Category 5, 5e, 6, 6a and 7 Cable Standards


 
Category 5 Cable

 

Category 5 (CAT5) cable is a multi-pair (usually 4 pair) high performance cable that consists of twisted pair conductors, used mainly for data transmission. Basic CAT5 cable was designed for characteristics of up to 100 MHz. CAT5 cable is typically used for Ethernet networks running at 10 or 100 Mbps.

 

 

Category 5e Cable

 

Category 5e (CAT5e) cable, also known as Enhanced Category 5, is designed to support full-duplex Fast Ethernet operation and Gigabit Ethernet. The main differences between CAT5 and CAT5e can be found in the specifications. The performance requirements have been raised slightly in the new standard (see comparison chart below).

 

CAT5e has stricter specifications for Power Sum Equal-Level Far-End Crosstalk (PS-ELFEXT), Near-End Crosstalk (NEXT), Attenuation, and Return Loss (RL) than those for CAT5. Like CAT5, CAT5e is a 100-MHz standard, but it has the capacity to handle bandwidth superior to that of CAT5. CAT5 cable is typically used for Ethernet networks running at 100 Mbps or 1 Gbps. 

 

Easy way to tell the difference between a Cat5e and Cat6 Patch Cable

 

cat5e vs cat6 patch cable, difference between cat5e and cat6 patch cable

       Cat6                          Cat5e      

 

 

Category 6 Cable

 

Category 6 (CAT6) cable provides higher performance than CAT5e and features more stringent specifications for crosstalk and system noise.

 

The quality of the data transmission depends upon the performance of the components of the channel. To transmit according to CAT6 specifications, jacks, patch cables, patch panels, cross-connects, and cabling must all meet CAT6 standards. The CAT6 components are tested individually, and they are also tested together for performance. In addition, the standard calls for generic system performance so that CAT6 components from any vendor can be used in the channel.

 

All CAT6 components must be backward compatible with CAT5e, CAT5, and CAT3. If different category components are used with CAT6 components, then the channel will achieve the transmission performance of the lower category. For instance, if CAT6 cable is used with CAT5e jacks, the channel will perform at a CAT5e level. 

 

 

Augmented Category 6 (CAT6a) Cable

 


CAT6a is a 10-Gigabit Ethernet over copper proposal to the CAT6 standard. The IEEE published a draft standard (Std 802.3an) in October 2004.  The draft calls for 10-Gigabit data transmission over a 4-pair twisted-pair copper cable for a distance of 100 meters on Class F or Class E-augmented copper cabling. The draft extends CAT6 electrical specifications from 250 MHz to 500 MHz. It also proposes a new measurement: Power-Sum Alien Crosstalk to 500 MHz. Alien Crosstalk is a coupled signal in a disturbed pair arising from a signal in a neighboring cable. 

 

The TIA is working to complete a new specification that will define enhanced performance standards for unshielded twisted pair cable systems. Draft specification ANSI/TIA/EIA-568-B.2-10 specifies cable systems, called "Augmented Category 6" or more frequently as "Category 6a", that operate at frequencies up to 500 MHz and will provide up to 10 Gbit/s bandwidth. The new specification has limits on alien crosstalk in cabling systems.

 

Augmented Category 6 specifies cable operating at minimum frequency of 500 MHz, for both shielded and unshielded. It can support future 10 Gb/s applications up to the maximum distance of 100 meters on a 4-connector channel.
Within the networking market place the move towards the ratification of Category 6 Augmented cabling is continuing, but with no firm standards set, it is a time to wait and see. Although a number of companies have announced Cat6A products, it is clear that these are purely based on proprietary systems, with a great deal of hope thrown in. The basic drive behind Cat6A is the desire to support 10Gbps to the desk over the standard 100m. Although the current Cat6 standard will support it up to 55m, this is not suitable for most organisations.

 

 

Category 7/Class F

 

 

Category 7/Class F (ISO/IEC 11801:2002) specifies a frequency range of 1–600 MHz over 100 meters of fully shielded twisted-pair cabling. It encompasses four individually shielded pairs inside an overall shield, called Shielded/Foiled Twisted Pair (S/FTP) or Foiled/ Foiled Twisted Pair (F/FTP). There is a pending class Fa, based on the use of S/FTP cable to 1000 MHz. It can support 10GBASE-T transmissions.

 

With both types of cable, each twisted pair is enclosed in foil. In S/FTP cable, all four pairs are encased in an overall metal braid. In F/FTP, the four pairs are encased in foil.

 

Category 7/Class F cable can be terminated with two interface designs as specified in IEC 6063-7-7 and IEC 61076-3-104. One is an RJ-45 compatible GG-45 connector. The other is the more common TERA connector, which was launched in 1999.

 

Category 7/Class F is backwards compatible with traditional CAT6 and CAT5 cable, but it has far more stringent specifications for crosstalk and system noise. The fully shielded cable virtually eliminates crosstalk between the pairs. In addition, the cable is noise resistant, which makes the Category 7/Class F systems ideal for high EMI areas, such as industrial and medical imaging facilities.  Category 7/Class F cable can also increase security by preventing the emission of data signals from the cable to nearby areas. 

http://www.fiberopticshare.com/wp-content/uploads/2018/09/cat6-vs-cat7-vs-cat8.png  

CategoryStandard BandwidthMax Data RateShielding
Cat5e100MHz (up to 350)1000MbpsUTP or STP
Cat6250MHz (up to 550)1000MbpsUTP or STP
Cat6A500MHz (up to 550)10GbpsUTP or STP
Cat7600MHz10GbpsShielded only
Cat82000MHz25Gbps or 40GbpsShielded only

 

 

Category 5, 5e, 6 & 7 Cable Comparison

CAT5

CAT5e

CAT6

   CAT6a  

CAT7 (Proposed)

Frequency

100 MHz

100 MHz

250 MHz

500 MHz

600 MHz

Attenuation (min. at 100 MHz)

22 dB

22 dB

19.8 dB

--

20.8 dB

Characteristic Impedance

100 ohms = 15%

100 ohms = 15%

100 ohms = 15%

--

100 ohms = 15%

NEXT (min. at 100 MHz)

32.3 dB

35.3 dB

44.3 dB

27.9 dB

62.1 dB

PS-NEXT (min. at 100 MHz)

NA

32.3 dB

42.3 dB

--

59.1 dB

EL-FEXT (min. at 100 MHz)

NA

23.8 dB

27.8 dB

9.3 dB

(not yet specified)

PS-ELFEXT (min. at 100 MHz)

NA

20.8 dB

24.8 dB

--

(not yet specified)

PS-ANEXT (min. at 500 MHz)

--

--

--

49.5 dB

--

PS-AELFEXT (min. at 500 MHz)

16 dB

20.1 dB

20.1 dB

23.0 dB

14.1 dB

Return Loss (min. at 100 MHz)

16 dB

20.1 dB

20.1 dB

8.0 dB

14.1 dB

Delay Skew (max. per 100m)

NA

45 ns

45 ns

--

20 ns

Networks Supported

100BASE-T

1000BASE-T

1000BASE-TX

10GBASE

(not yet specified)


Go Back 】 | 【 Print 】 | 【 Close this window

Contact us
Tel: +86-13480988514
ADD: FL.#6, F1, Building#3, Shangxiawei Industrial Park, Shasan Road, Shajing, Bao'an District, Shenzhen, Guangdong, China
Official Social Media
Shenzhen OUTENGDA Electronic Technology Co., Ltd. Shenzhen OUTENGDA Electronic Technology Co., Ltd. Shenzhen OUTENGDA Electronic Technology Co., Ltd. Shenzhen OUTENGDA Electronic Technology Co., Ltd. Shenzhen OUTENGDA Electronic Technology Co., Ltd.
Copyright © Shenzhen OUTENGDA Electronic Technology Co., Ltd. All Rights Reserved.
Links:
Facebook | Twitter | Linkedin | Google+ | youtube | add more link |